Finelite
Product ShortcutsProduct Shortcuts|Media Center|Agent Login|Contact|Home
2x2
2x2
3x3
3x3
4x4
4x4
Overview Options Specifications Images

Photometry

HPT 3x3 Photometry

HPT 3x3
3500K, Very High Output (V)
Total lumens: 10791
Lumens per watt: 131

HPT - 3x3 Specifications

BODY TYPE

CONSTRUCTION
Die-formed 20-gauge cold-rolled steel housing. Lift and shift lens provides easy access to light arrays and driver compartment for servicing from below. Seismic brackets are integrated into the luminaire assembly. Additional wire entrances are posi-tioned on the ends of the housing to allow easy wiring access for the installer.

SIZES
HPT is available in 2'x2', 3'x3', and 4'x4' sizes.

ARRAY TYPE

LIGHT OUTPUT
Four lumen packages available. Standard (S), Boosted Standard (B), High (H), and Very High (V). A separate chart summarizes lumen distribution and wattage. Light engines are replaceable.

MECHANICAL FEATURES

OPTICAL SYSTEM
2'x2' diffusers are UV- stabilized and impact-resistant frosted virgin acrylic, 0.08" Thick. 3'x3' & 4'x4'diffuser thickness - 0.118".

LUMEN MAINTENANCE 90% of initial light output (L90) at 100,000+ hours; 70% of initial light output (L70) at 200,000+ hours.

ELECTRICAL FEATURES

STATIC FEED
Standard with Lead Wires. Optional whips (with flex connectors) supplied in a maximum of 11' lengths, standard whip length is 6'.

TUNABLE WHITE FEED
Standard with Lead Wires. DMX and power feed at same location (standard). Optional whips (with flex connectors) supplied in a maximum of 11' lengths, standard whip length is 6'. DMX feeds cannot be cut or spliced. DMX feeds should be ordered based on fixed lengths.

STATIC DRIVER
Replaceable 120V/277V Constant Current Reduction dimming driver standard. Can be wired dimming or non-dimming. 0-10V dimming controls with a range of 10%- 100% standard. Dimming to 1% available. Driver is fully accessible from below the ceiling. Power Factor: ≥0.9. Total Harmonic Distortion (THD) < 20%. Expected driver lifetime: 100,000 hours.

TUNABLE WHITE DRIVER
Replaceable LED driver accessible from below the ceiling. 120/277V. Power factor ≥0.90. Total Harmonic Distortion (THD): <20%. Dimming Range: 100% - 1%. Expected driver lifetime: 100,000 hours.

LUTRON STATIC DRIVER OPTIONS
LUTES1 (Hi-lume 1% EcoSystem with Soft-On, Fade to Black dimming (LDE1 series)); LUTES5 (5-Series 5% EcoSystem (LDE5 Series)), LUT2W (Hi-lume 1% 2-wire, 120V forward phase dimming (LTEA series)); Contact factory for availability of discontinued Lutron drivers, L3DA-3-wire and L3DA EcoSystem.

LUTRON TUNABLE WHITE DRIVER OPTION
LUTDTW (1% T-Series 2-Channel Digital Tunable White (PSQ Series)).

SENSORS
On-board sensors not available.

 
MOUNTING TYPE

T-BAR MOUNT
Standard flange design works with most lay-in ceiling types. Integral pry-out tabs secure the luminaire to the ceiling grid from above. The location of the pryout tabs allows two luminaires to be mounted adjacent to each other sharing the same T-bar. Tie-in locations for tie-wire on all corners. Consult local code for appropriate tie-wire recommendations. Drywall Kit available.

SURFACE MOUNT (2'X2' ONLY)
Lay-in ceiling types: caddy clip with 1/4 - 20 stud and nut. Drywall or concrete surfaces (walls or ceilings): 1/4 - 20 stud and nut (provided by others). Luminaire is compatible with recessed junction boxes. Electrical connections can be made directly to wiring access plate. Center of feed location is coincident with the center of the luminaire.

PENDANT MOUNT (2'X2' ONLY)
50" Fully Adjustable (FA) plated steel aircraft cable with safety stop hardware standard. Contact factory for additional lengths up to 300".

TUNABLE WHITE DMX MOUNTING
For grid ceiling applications the dual GridBox™ mounting is supplied (standard). For hard ceiling applications the ceiling mounting box is supplied (standard). DMX feeds cannot be cut or spliced. DMX feeds should be ordered based on fixed lengths. Available DMX pendant feed lengths are 5', 12', and 30' (5' standard).

TUNABLE WHITE DMX INTERCONNECTION CABLES
Luminaires are prewired with plug-and-play interconnection cables to support easy plug-together joining of luminaire runs. If a non-FineTune DMX system has been specified, a DMX to RJ45 converter is provided.

OTHER FEATURES

EMERGENCY STYLE
Optional emergency to generator/inverter wiring, nightlight wiring, stepdimming driver (available for B & V outputs only), and Chicago Plenum option are available for all sizes.

Available for 2'x2' only: Internal generator transfer switch, Factory Choice low-profile backup battery, or Bodine BSL722 battery pack. Backup batteries deliver 1600 lumens and illuminate a 1'x2' section.

TUNABLE WHITE ELECTRICAL
Emergency Option DMX: Battery backup only (Emergency to generator/inverter wiring available when using Finetune DMX driver and TCS control system).

Emergency Option DALI: Battery backup, emergency-to-generator/ inverter wiring.

Emergency Option Lutron: Battery backup, emergency-to-generator/inverter wiring.

Emergency Option PoE: Contact factory.

Finelite Home LinkedInFacebookTwitterYouTubePinterestInstagram A brand of Legrand

© Finelite, Inc. All rights reserved.    Contact Us  |  Privacy Policy  |  Sales Terms and Conditions  |  Site Map