CONSTRUCTION
Fixture channel is 6063-T6 extruded aluminum. Fascia covers are die-formed 20-gauge steel. Mounting clips are constructed from 22-gauge die-formed steel. All components are hard-tooled to tolerances of +/- 0.010".
ENDCAPS
Flat endcap, 14-gauge die-formed steel, adds 0.1" to each end.
REFLECTORS
96W standard reflector, die-formed painted steel, 96% reflectance white finish. Virgin acrylic UV stabilized lensed diffuser behind perforated fascia is standard.
DIFFUSERS
Standard with top 0.080" and bottom 0.060" frosted acrylic diffusers
LIGHT OUTPUT
Four lumen packages available, Standard Output (S), Boosted Standard Output (B), High Output (H), and Very High Output (V). A separate chart summarizes lumen distribution and wattage. Light engines are replaceable.
LUMEN MAINTENANCE
90% of initial light output (L90) at 100,000+ hours; 70% of initial light output (L70) at 200,000+ hours.
DRIVER
Replaceable 120V/277V Constant Current Reduction dimming driver standard. Can be wired dimming or non-dimming. 0-10V dimming controls with a range of 10%- 100%. Dimming to 1% available; consult factory. Driver is fully accessible from below the ceiling. Power Factor: ≥0.9. Total Harmonic Distortion (THD) < 20%. Step-dimming driver (limited programable outputs. Contact Factory). Expected driver lifetime: 100,000 hours.
LUTRON DRIVER OPTIONS
LutES1 (Hi-lume 1% EcoSystem with Soft-On, Fade to Black dimming (LDE1 series)); LutES5 (5-Series 5% EcoSystem (LDE5 Series)), Lut2W (Hi-lume 1% 2-wire, 120V forward phase dimming (LTEA series)); Contact factory for availability of discontinued Lutron drivers, L3DA-3-wire and L3DA EcoSystem.
ELECTRICAL
Optional emergency to generator/inverter wiring, internal generator transfer switch, nightlight wiring, backup battery. Factory-choice, low-profile, battery backup delivers 1337 lumens (ACF) or 1611 (VCF) for Solid Fascia (SF) and 1653 lumens (ACF) or 1798 (VCF) for Perforated Fascia (PF). Minimum luminaire length for battery pack: 8’. The downlight alway will be illuminated in the 4' section.
INTEGRATED SENSORS
Available with integrated ultrasonic occupancy sensors. Not available on 2’ luminaries.